Vista de pagina 124
6-11
CH 6/ Advanced Setup Options
Procedure to
record rms
variation
(continued)
Continued on next page
Action... Result...
STEP 3: Users can define the number
of rms summary and waveform
cycles to be saved before the start
(pre-), after the start (post-start), and
after the end (post-end) of the event.
The Pre- and Post- trigger settings
under Waveform Capture (Cycles)
specify the number of waveform
cycles to record before, during, and
after the event. Although waveform
cycle recording is enabled by default,
users have the option not to record
waveform cycles.
Press Enable to turn waveform
cycle recording on/off.
Press any Pre- or Post- trigger cycle
field. Use the numeric keypad to
enter the cycle counts for
corresponding rms sample/waveform
cycle capture.
RMS Summary (Cycles):
Press Pre-Trigger to set the
number of cycles for Pre-event
start rms samples. This setting is
also used for Pre-event end cycles.
Use the keypad to enter the
number of cycles of rms samples
to record before the event start
trigger cycle.
Press In-Out Post to set the
number of cycles for Post-event
start cycles. Use the keypad to
enter the number of cycles to
record after the event start cycle.
The maximum number of cycles to
record is 100 cycles.
Press Out-In Post to set the
number of cycles for Post-event
end cycles. Use the keypad to
enter the number of cycles to
record after the event end point.
The maximum number of cycles to
record is 100 cycles.
MARK112_209