8-12
Compliance History, continued
Compliance
History table
(continued)
Evaluation Period
: Displays the date and time of the beginning of the evaluation period.
Each evaluation period is independent of each other. The default length of evaluation
period is a 7-day week period by which the unit calculates information in strict
compliance with the EN50160 standard.
Compliance
: Displays a PASS (green) or FAIL (red) mark if evaluation is done for a
complete 7-day week period. Compliance displays an Undetermined (black) mark for
incomplete periods. A PASS or FAIL compliance status is hyperlinked to the
Compliance Statistical Bar Chart that shows the seven parameters required for
determining compliance. See Compliance Statistical Bar Chart on page 8-8.
RMS Event Count
: Details of rms variation event count are shown in the EN50160
DISDIP table on page 8-13.
Transient Event Count
: The complete table for Transient Overvoltages appears in the
EN50160 DISDIP table on page 8-14.