Dran-View 6 User Guide
Advanced
Category
G5/4 Prediction of a new nonlinear load/Harmonics against limits
Page 1
Enterprise
Edition
Only
This page allows you to enter the
current harmonics (Amps) for a new
non-linear load. The manufacturer of
the new equipment usually supplies
these figures. The predicted voltage
harmonics are calculated from the
given current harmonics. The predicted
and the measured voltage harmonics
are then summed up and may be
compared against the G5/4 planning
levels (limits).
This module was implemented for the UK market, but may be useful for others.
It is based on the “ENGINEERING RECOMMENDATION G5/4 February
2001”.
Do you want to predict Voltage Harmonics for a new non-linear load?
You need to check this option to activate this page. If it is not
checked, you will still be able to proceed to the next
(comparison) page. However you will only compare measured
harmonics without the influence of predicted harmonics.
Nominal system
voltage
Only the following options can be selected: 400V, 6.6kV,
11kV, 20 kV, or 22 kV.
Cumulative
threshold(1-
100%)
This edit-box should contain a statistical value between 1-
100%. Most power quality standards include information about
this number; usually 95% or 100% is used. If a value other
than 100% is used, some fluctuations are filtered out. A 95%
value means that the worst (highest) 5% is excluded.
Open / Save Use these buttons to load or save you settings to a file (.DLM).
Continued on the next page