DB-PX5 - PowerVisa 440® / PowerGuide® 4400 / PowerXplorer® PX5 Op. Skills
© 2006-2010 by PowerCET Corporation. All rights reserved. (100616)
46
©2006-2008 PowerCET Corporation. All rights reserved.
91
RMS triggers occur when any
one of the measured quantities
crosses the high or low limit for a
period of at least one rms sample
point (which are taken twice per
cycle with a one cycle sliding
integration window)
Disturbance End = the cycle
when all triggered channels
return within limits for a minimum
duration of cycles specified in
range to end event. Until then,
any subsequent excursions
beyond the thresholds are
considered part of the original
disturbance. To minimize the
number of triggers recorded for a
sequence of closely spaced
disturbances, hysteresis is
employed in both voltage and
time for the begin-event and end-
event thresholds
Press: RMS Variation Limit
Wizard Setup: RMS Variation Limits
©2006-2008 PowerCET Corporation. All rights reserved.
92
If applicable, Press: Group
A B C to simplify setup
Press the threshold
parameter (High, Low, Very
Low) to change, enable or
disable threshold values
High limits must be at least
.1 higher than Low limits, or
the entered value will not
be accepted.
Press: % of Nominal to use
percentages instead of
volts
Press the other tabs to set
other channels
Press: Amps
Wizard Setup: RMS Variation Limits